  • HHD1-1A, 1, 1B motor protectors

    HHD1-1A, 1, 1B motor protectors

    Working power supply:AC220V、AC380V  50Hz

    Current range:-1A:1~5A  -1:4~20A  -1B:16~80A

    Protection function:Phase break, three-phase unbalance, overload, blocked rotation, starting avoidance

    Display mode:LED digital tube displays maximum phase current and memory fault status

    Display accuracy:Level 2.0

    Setting method:Potentiometer static quantization setting

    Reset mode:The panel is reset or powered off

    Trip grade:2, 5... 40 Continuously adjustable

    Contact form:A set of normally open normally closed switching contacts

    Contact capacity:3A AC380V(Resistive)

    Overall dimensions:125×71×120mm

    Installation method:Device and rail compatible

    Optional features:Ground (code J with special zero-sequence transformer) or 4-20mA transmission output (code B)

    HHD1F-C motor protector

    HHD1F-C motor protector

    Working power supply:AC220V、AC380V  50Hz

    Current range:-C:20~300A

    Protection function:Starting avoidance, phase break, three-phase unbalance, overload (fixed time limit inverse time limit), lock-in, underload, grounding

    Display mode:LED nixie displays maximum phase current and fault status indication

    Display accuracy:Level 2.0

    Setting method:Key setting

    Reset mode:Panel reset or power off reset and automatic reset

    Contact form:A group of independent normally open and normally closed

    Contact capacity:3A AC380V(Resistive)

    Overall dimensions:154×65×157mm

    Installation method:Device type

    Optional features:Ground (code J with special zero-sequence transformer) or 4-20mA transmission output (code B)

    Note:Replace HHD1 series, HHD3i series, HHD3H series

    HHD1F-A, B motor protectors

    HHD1F-A, B motor protectors

    Working power supply:AC220V、AC380V  50Hz

    Current range:-A:0.5~6.5A  -B:1~100A

    Protection function:Starting avoidance, phase break, three-phase unbalance, overload (fixed time limit inverse time limit), lock-in, underload, grounding

    Display mode:LED nixie displays maximum phase current and fault status indication

    Display accuracy:Level 2.0

    Setting method:Key setting

    Reset mode:Panel reset or power off reset and automatic reset

    Contact form:A group of independent normally open and normally closed

    Contact capacity:3A AC380V(Resistive)

    Overall dimensions:125×71×120mm

    Installation method:Device type and 35mm rail type compatible

    Optional features:Ground (code J with special zero-sequence transformer) or 4-20mA transmission output (code B)

    Note:Replace HHD1 series, HHD3i series, HHD3H series

    HHD1-2, 3, 3A motor protectors

    HHD1-2, 3, 3A motor protectors

    Working power supply:AC220V、AC380V  50Hz

    Current range:-2:20~100A  -3:40~200A  -3A:60~300A

    Protection function:Phase break, three-phase unbalance, overload, blocked rotation, starting avoidance

    Display mode:LED digital tube displays large phase current and memory fault status

    Display accuracy:Level 2.0

    Setting method:Potentiometer static quantization setting

    Reset mode:The panel is reset or powered off

    Trip grade:2, 5... 40 Continuously adjustable

    Contact form:A group of normally open and a group of normally closed independent contacts

    Contact capacity:3A AC380V(Resistive)

    Overall dimensions:154×65×157mm

    Installation method:Device type

    Hot product / Hot Products

    Recommendation information / Recommended News

    The research team of the United Front Work Department of the CPC Yueqing Municipal Committee visited Devil's 13 Electric to carry out a special research on

    The research team of the United Front Work Department of the CPC Yueqing Municipal Committee visited Devil's 13 Electric to carry out a special research on "Two health" culture

    The research team of the United Front Work Department of the CPC Yueqing Municipal Committee visited Devil's 13 Electric to carry out a special research on "Two health" culture

    On October 17, Zheng Juhua, member of the Standing Committee of Yueqing Municipal Committee and Minister of the United Front Work Department, and Ye Rupeng, vice minister of the United Front Work Department, visited Devil's 13 Electric to carry out a cultural research on "two health". Hu Zhixing, chairman of Devil's 13 Electric, and Huit, vice president of Devil's 13, accompanied the research. 【 More details 】

    Contact Devil's 13Contact

    Hotline:400-8236-775

    Phone:0577-6273 5555

    Fax:0577-6272 2963

    Email:[email protected]

    Company Address:No. 328, Wei19 Road, Yueqing Economic Development Zone, Zhejiang

    Baidu
    map